Droplet Size of Cooling Tower Fog

&
Pages 191-203 | Received 16 May 1975, Accepted 30 May 1975, Published online: 02 Sep 2009
 

Abstract

Fog from cooling towers causes problems of visibility and icing along roadways adjacent to the towers; moreover, the visible plume from the towers offers difficulty in that it is equated by much of the public with air pollution. It is desirable to know the size of the fog droplets in order to plan abatement procedures and to determine the airborne lifetimes of such fogs.

The methodology involved capturing the droplets on slides coated with a vaseline-mineral oil mixture, making photomicrographs of the droplets, counting and sizing the droplets into eight droplet diameter increments; namely, <5 μm, 5–10 μm, 10–20 μm, 20–40 μm, 40–60 μm, 60–80 μm, 80–100 μm, and >100 μm. The resulting distribution was similar to that for natural fogs and clouds; i.e., it was bi-modal, the first mode at <5 μm containing the vast majority of the droplets, and the second at 20–40 μm. This study agrees with others that the size distribution of a fog in a saturated environment is continuously changing, with the smaller droplets tending to evaporate and the larger ones tending to grow, thus shifting the second mode toward larger sizes.

Reprints and Corporate Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

To request a reprint or corporate permissions for this article, please click on the relevant link below:

Academic Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

Obtain permissions instantly via Rightslink by clicking on the button below:

If you are unable to obtain permissions via Rightslink, please complete and submit this Permissions form. For more information, please visit our Permissions help page.