An Extension of the Flow Boiling Correlation to Transition, Laminar, and Deep Laminar Flows in Minichannels and Microchannels

&
Pages 86-93 | Published online: 17 Aug 2010

Abstract

Flow boiling in mini- and microchannels offer very high heat transfer capabilities and find applications in many emerging technologies, such as electronics cooling and fuel cells. The low flow rate employed in such geometries, coupled with the small flow channels, often results in a laminar flow with all flow as liquid. Since the single-phase flow with all liquid is in the laminar range, the flow boiling correlations developed for conventional tubes with an inner diameter larger than 3 mm and turbulent flow need to be carefully reviewed. In the present work, flow boiling correlation for large diameter tubes developed by Kandlikar [Citation1,Citation 2] is modified for flow boiling in minichannels by using the laminar single-phase heat transfer coefficient for all liquid flow. The correlation is also extended for flow boiling in microchannels using the nucleate boiling as the dominant part of the original correlation. The trends in heat transfer coefficient versus quality are compared in the laminar and deep laminar regions in minichannels and microchannels. Excellent agreement is obtained between predicted values and experimental data.

The original correlation by Kandlikar [Citation1,Citation 2] on flow boiling heat transfer coefficient was developed using a large data bank consisting of over 10,000 data points. The tube diameter ranged from 3 to 25 mm. All the data was in the turbulent region (ReLO > 3000) considering all flow in the liquid phase. With the current interest in minichannels and microchannels, the correlation is extended to these geometries. The available experimental data is used to verify the validity of the extended correlation.

As the tube diameter becomes smaller, the practical range of all liquid flow Reynolds number (ReLO) falls in the laminar region. shows the range of the Reynolds number as a function of tube diameter using some of the flow boiling data available in literature. It is seen from that for tube diameters below 1 mm, ReLO extends well into the laminar region. For microchannels with diameters below 200 micrometers, the all-liquid flow is invariably in the laminar region.

FIG. 1 Ranges of Reynolds Number, ReLO, employed in various experimental investigations (Kandlikar [Citation12]).

FIG. 1 Ranges of Reynolds Number, ReLO, employed in various experimental investigations (Kandlikar [Citation12]).

The channel size classification used in this work follows the recommendations of Kandlikar and Grande [Citation3] given below:

  • Conventional channels: Dh ≥ 3 mm

  • Minichannels: 200 μm ≤ Dh < 3 mm

  • Microchannels: 10 μm ≤ Dh < 200 μm

  • Transitional Channels: 0.1 μm < Dh < 10 μm

  • Transitional Microchannels: 1 μm < Dh ≤ 10 μm

  • Transitional Nanochannels: 0.1 μm < Dh ≤ 1 μm

  • Molecular Nanochannels: Dh ≤ 0.1 μm

The classification is based on the mean free path of molecules in the single-phase flow, surface tension effects, and flow patterns in the two-phase flow applications. It should be emphasized that the channel size classification is merely a guide to help us identify the channel size ranges in various applications. The operating parameters, such as system pressure, and fluid properties, such as density, viscosity, and surface tension, have a major influence on the flow characteristics. These classifications are not linked to any specific equations. Nevertheless, it serves as a guide in identifying the physical dimensions associated with the flow phenomena in a somewhat general way.

In the present work, the applicability of the Kandlikar correlation [Citation1,Citation 2] is extended to the minichannels and microchannels by suitably accounting for the low Reynolds number values encountered in these geometries.

ORIGINAL CORRELATION FOR LARGE DIAMETER TUBES (ReLO > 3000)

Flow boiling heat transfer correlations, such as those in Kandlikar [Citation1,Citation 2], utilize the single-phase, all-liquid heat transfer coefficient in predicting the nucleate boiling and convective boiling components as given by the following equation,

(1)
(2)
(3)
The single-phase, all-liquid flow heat transfer coefficient hLO is given by the following correlations by Petukhov and Popov [Citation4] and Gnielinski [Citation5], respectively.
(4)
(5)
where f is the friction factor given by
(6)
FFl is a fluid-surface dependent parameter. This parameter represents the nucleation characteristics of the liquid on the given heater surface, which depend on the nucleation site density, fluid properties responsible for nucleation, etc. However, since such information is not available in the flow boiling data, it has been correlated against the fluid-surface combinations for commercial tube surfaces. gives the values of FFl for a number of fluids on copper and brass surfaces.

Table of recommended FFl (fluid-surface parameter) values in flow boiling correlation by Kandlikar [Citation1,Citation 2]

The Kandlikar correlation [Citation1,Citation 2] was developed using a large data bank consisting of over 10,000 local data points with ten different fluids, including water, refrigerants, and cryogenic fluids. The success of the Kandlikar correlation in accurately representing the trends in heat transfer coefficient versus quality is seen with the high pressure and low pressure data obtained by Schrock and Grossman [Citation6]. compares the flow boiling data from the Schrock and Grossman [Citation6,Citation 7] and Kandlikar [Citation1] correlation. The all-liquid flow heat transfer coefficient is calculated using the turbulent flow correlation. The correlation predicts Schrock and Grossman's data within less than 10%, and the trends are also well represented.

FIG. 2 Dependence of heat transfer coefficient on x; comparison of Schrock and Grossman [Citation6,Citation 7] data with Kandlikar [Citation1,Citation 2] correlation.

FIG. 2 Dependence of heat transfer coefficient on x; comparison of Schrock and Grossman [Citation6,Citation 7] data with Kandlikar [Citation1,Citation 2] correlation.

The nucleate boiling and convective boiling contributions are additive in flow boiling. The overall trend in heat transfer coefficient versus quality is that nucleate boiling contribution decreases with quality and convective boiling contribution increases with quality. Depending on the boiling number and the liquid to vapor density ratio, the heat transfer coefficient trends are seen to be increasing, decreasing or flat with an increase in quality. This insight led to the development of a flow boiling map presented by Kandlikar [Citation8].

In a subsequent paper, Kandlikar [Citation2] showed that the single-phase heat transfer coefficient hLO should be treated as the single-phase heat transfer coefficient with all flow as liquid at any given section. Based on this concept, Kandlikar successfully extended the correlation to predict the flow boiling heat transfer coefficients in microfin tubes and compact heat exchanger geometry. The correlation predicts contribution from the nucleate boiling term even under high quality. In an effort to validate the presence of nucleation under high shear conditions, Kandlikar et al. [Citation9] conducted high speed video imaging for water boiling over a 10 mm diameter circular heated rod, placed flush in the 40 mm × 3 mm rectangular channel. The video images showed the presence of bubbles as small as 10 microns evolving rapidly under highly sheared flow conditions.

In the subcooled flow boiling region, the flow boiling was seen as fully developed at higher wall superheats. Considering only the nucleate boiling term in the nucleate boiling dominant part of the correlation, Kandlikar [Citation10] predicted the subcooled flow boiling data.

However, one of the major limitations of the correlation was that it was applicable only to the turbulent flow data (with ReLO in the turbulent region). Following the suggestion made by Kandlikar [Citation2], the extension presented in the following section provides a complete correlation scheme for deep laminar, laminar, and transition region flows in minichannels and microchannels.

CORRELATION EXTENSION TO LAMINAR AND TRANSITION FLOW REGION IN MINICHANNELS (1600 < ReLO > 3000)

gives the list of selected experimental data for flow boiling heat transfer studies in mini- and microchannels. In two recent investigations, Kandlikar and Steinke [Citation11,Citation 12] extended the range of applicability of the Kandlikar [Citation1,Citation 2] correlation (EquationEq. (1)) to Reynolds numbers below 3000. It is necessary for the all-liquid flow single-phase heat transfer coefficient to reflect the existing single-phase flow structure. The use of turbulent flow correlations was not appropriate when the flow is laminar. A transition region was identified between Reynolds numbers of 1600 and 3000, and the following recommendations were made:

  • Turbulent region: ReLO ≥ 3000

  • Transition region: 1600 ≤ ReLO < 3000

  • Laminar region: ReLO < 1600

The single-phase heat transfer coefficient for all flow as liquid, hLO, was calculated in the above regions as follows:
  • Turbulent region: Gnielinski correlation

  • Transition region: Depends on other flow parameters—a linear interpolation between ReLO of 1600 and 3000 is recommended.

  • Laminar region: Laminar flow equation, Nu = C

For flow boiling in small diameter tubes, the effect of tube orientation is negligible, and the Froude number effect in the above correlation is deleted by setting f2(Fr LO) = 1.

TABLE 2 Selected flow boiling heat transfer studies for mini- and microchannels

The resulting correlation takes the following form:

(7)
(8)
For ReLO < 1600, the flow is considered as laminar, and the following equation is used for calculating the single-phase all-liquid laminar heat transfer coefficient, hLO
(9)
For the transition region, a linear interpolation between the turbulent single-phase heat transfer coefficient and laminar heat transfer coefficient values is recommended as described earlier. Another fact that is observed in all the flow boiling data with small channels is that the first two or three experimental data points at low qualities always report considerably higher heat transfer coefficient values. This is believed to be due to the increased heat transfer rate associated with the onset of nucleate boiling. This effect is not predicted by the correlation. Also, the correlation is not valid in the liquid deficient region at high qualities, generally observed to be above 0.7 to 0.8.

compares the flow boiling data from Wambsganss et al. [Citation15] with the correlation by Kandlikar [Citation1,Citation 2] using turbulent single-phase correlation. It is seen that the correlation by Kandlikar [Citation3,Citation 4] using a turbulent single-phase heat transfer coefficient yields good agreement. The average deviation between the data and the correlation is 19.7%.

FIG. 3 Wambsganss et al. [Citation15] R113 data (points) compared to the present correlation (lines) using turbulent (Dittus-Boelter) single-phase correlation; Dh = 2.92 mm, Psat = 150 kPa, and ReLO = 1,995, 2,013, and 1,934 (Kandlikar et al. [Citation11]).

FIG. 3 Wambsganss et al. [Citation15] R113 data (points) compared to the present correlation (lines) using turbulent (Dittus-Boelter) single-phase correlation; Dh = 2.92 mm, Psat = 150 kPa, and ReLO = 1,995, 2,013, and 1,934 (Kandlikar et al. [Citation11]).

compare the flow boiling data from Lin et al. [Citation14] with the correlation by Kandlikar [Citation1,Citation 2]. It is seen that as the Reynolds number is reduced from the transition region (ReLO = 1970) to laminar region (ReLO = 1156), the data start to yield good agreement with the correlation by Kandlikar [Citation1,Citation 2] using a single-phase all-liquid laminar heat transfer coefficient. The average deviation between the prediction and the data is 21.9%. Although this deviation is somewhat high, it should be recognized that the transition region tends to be quite difficult to predict even for the single-phase flow.

FIG. 4 Flow boiling data of Lin et al. [Citation14] compared to the correlation by Kandlikar (1990, 1991a) using laminar and turbulent single-phase correlations; Dh = 2 mm, q″ = 40.2 kW/m2, and ReLO = 1970 (Kandlikar et al. [Citation11]).

FIG. 4 Flow boiling data of Lin et al. [Citation14] compared to the correlation by Kandlikar (1990, 1991a) using laminar and turbulent single-phase correlations; Dh = 2 mm, q″ = 40.2 kW/m2, and ReLO = 1970 (Kandlikar et al. [Citation11]).

FIG. 5 Flow boiling data of Lin et al. [Citation14] compared to the correlation by Kandlikar [Citation1,Citation 2] using laminar and turbulent single-phase correlations; Dh = 1.1 mm, q″ = 36.2 kW/m2, and ReLO = 1600 (Kandlikar et al. [Citation11]).

FIG. 5 Flow boiling data of Lin et al. [Citation14] compared to the correlation by Kandlikar [Citation1,Citation 2] using laminar and turbulent single-phase correlations; Dh = 1.1 mm, q″ = 36.2 kW/m2, and ReLO = 1600 (Kandlikar et al. [Citation11]).

FIG. 6 Flow boiling data of Lin et al. [Citation14] compared to the correlation by Kandlikar [Citation1,Citation 2] using laminar and turbulent single-phase correlations; Dh = 1.1 mm, q″ = 34.6 kW/m2, and ReLO = 1156 (Kandlikar et al. [Citation11]).

FIG. 6 Flow boiling data of Lin et al. [Citation14] compared to the correlation by Kandlikar [Citation1,Citation 2] using laminar and turbulent single-phase correlations; Dh = 1.1 mm, q″ = 34.6 kW/m2, and ReLO = 1156 (Kandlikar et al. [Citation11]).

CORRELATION EXTENSION TO LOW REYNOLDS NUMBER FLOWS IN MINICHANNELS (410 > ReLO > 100)

In a recent work, Kandlikar and Balasubramanian [Citation15] extended the correlation by Kandlikar [Citation1,Citation 2] to laminar flow in minichannels. The correlation by given EquationEqs. (4) and (8) using the single-phase laminar all-liquid flow heat transfer coefficient hLO is used for the low Reynolds number flow in minichannels. The single-phase laminar all-liquid flow heat transfer coefficient hLO is given by EquationEq. (5).

compares the flow boiling data from Yen et al. [Citation16] with the correlation by Kandlikar [Citation1,Citation 2] using a laminar single-phase equation. A circular tube of diameter 0.51 mm (510 μm) is used in these data sets. The data yield reasonable agreement with the correlation but the trend seems to be changing. As the Reynolds number is decreased to lower values, the correlation starts to over predict the data, especially in the high quality region. This indicates that the convective boiling contribution is reduced at a lower Reynolds number.

FIG. 7 Yen et al. [Citation16] data point for HCFC 123 compared to the correlation by Kandlikar [Citation1,Citation 2] using laminar single-phase equation; Dh = 0.51 mm, G = 295 kg/m2 s, and ReLO = 410 (Kandlikar et al. [Citation15]).

FIG. 7 Yen et al. [Citation16] data point for HCFC 123 compared to the correlation by Kandlikar [Citation1,Citation 2] using laminar single-phase equation; Dh = 0.51 mm, G = 295 kg/m2 s, and ReLO = 410 (Kandlikar et al. [Citation15]).

The agreement with the experimental data is 16.3% in the laminar region above ReLO = 400. The trend also is undergoing a change from its convective boiling dominant trend of flat or slightly increasing to the nucleate boiling trend of decreasing h versus x as the flow Reynolds number decreases, which can be seen from . In this region, the changeover from one trend to another show somewhat contradictory results. However, a further decrease in the Reynolds number leads to the nucleate boiling dominant trend with its characteristic decreasing h versus x trend, as shown in the following section.

FIG. 8 Yen et al. [Citation16] data point for HCFC 123 compared to the proposed correlation using laminar single-phase equation; Dh = 0.19 mm, G = 145 kg/m2 s, and ReLO = 105 (Kandlikar et al. [Citation15]).

FIG. 8 Yen et al. [Citation16] data point for HCFC 123 compared to the proposed correlation using laminar single-phase equation; Dh = 0.19 mm, G = 145 kg/m2 s, and ReLO = 105 (Kandlikar et al. [Citation15]).

FIG. 9 Yen et al. [Citation16] data point for HCFC 123 compared to the proposed correlation using laminar single-phase equation; Dh = 0.19 mm, G = 145 kg/m2 s, and ReLO = 86 (Kandlikar et al. [Citation15]).

FIG. 9 Yen et al. [Citation16] data point for HCFC 123 compared to the proposed correlation using laminar single-phase equation; Dh = 0.19 mm, G = 145 kg/m2 s, and ReLO = 86 (Kandlikar et al. [Citation15]).

CORRELATION EXTENSION TO VERY LOW REYNOLDS NUMBERS IN MICROCHANNELS (ReLO ≤ 100)

In the same work, Kandlikar and Balasubramanian [Citation15] also extended the correlation by Kandlikar [Citation1,Citation 2] to deep laminar flow, ReLO ≤ 100, in microchannels. In this range, the following correlation is recommended:

(10)
where hTP,NBD is given by EquationEq. (7), reproduced below:
(11)
The single-phase laminar all-liquid flow heat transfer coefficient hLO is given by EquationEq. (5). The proposed correlation given by EquationEqs. (10–11) takes into account the nucleate boiling dominant region (h TP,NBD) of the previous Kandlikar correlation, EquationEqs. (7–8), without any additional constants. The convective part of the correlation is neglected. The proposed correlation indicates that the flow is dominated by nucleate boiling for ReLO ≤ 100 in microchannels.

A circular tube of diameter 0.19 mm (190 μm) is used in the data sets presented in . The proposed correlation is denoted by the legend Laminar-NBD in figures, which refers to laminar flow with the nucleate boiling dominant correlation. The trend displayed in the data for the low quality region warrants some discussion. Immediately following the nucleation, or the onset of nucleate boiling, the liquid super heat is suddenly released, which results in a very high heat transfer coefficient in the low quality region.

The proposed Kandlikar and Balasubramanian correlation [Citation15] yields excellent agreement, as seen in , which both have ReLO around 100. Based on this behavior, it can be concluded that the boiling is nucleate dominant for low Reynolds number flow in microchannels (ReLO ≤ 100). The average deviation between the experimental data and the correlation prediction in the deep laminar region is 17.3%.

CONCLUSION

  1. The work by Kandlikar and Steinke [Citation11,Citation 12] extends the range of the correlation by Kandlikar [Citation1,Citation 2] to laminar and transition flow in minichannels by introducing the use of the fully developed laminar and transition flow equations for the all-liquid flow heat transfer coefficient. The new sets of equations are given by EquationEqs. (7–8) with an appropriate single-phase correlation for hLO.

  2. The transition between the laminar and turbulent flow, as seen through the single-phase all-liquid flow correlation, is not well defined. In general, the flow with ReLO < 1600 may be treated as fully developed laminar flow, while the flow may be considered in the transition region for 1600 ≤ ReLO < 3000. The Gnielinski correlation is applicable for ReLO > 3000. An appropriate interpolation scheme needs to be developed in the transition region.

  3. The experimental data for 0.51 mm diameter tubes (minichannel) for low laminar flow (450 > ReLO > 150) was well correlated using the Kandlikar correlation [Citation1,Citation 2] with hLO calculated from laminar flow equation.

  4. The experimental data for 0.19 mm diameter tubes (microchannel) for deep laminar flows (ReLO ≤ 100) was also well correlated using the proposed correlation, which uses only the nucleate boiling dominant part of the Kandlikar correlation, EquationEqs. (10–11). The average deviation between the experimental data and the correlation in various regions is found to be less than 20%.

  5. Based on the data sets investigated using the proposed correlation, it is concluded that boiling is more nucleate dominant for low Reynolds number flows (ReLO ≤ 100) in microchannels.

  6. More experimental data is needed to verify the nucleate boiling dominant effect in the low Reynolds number flow in minichannels. Also, the exact transition to the NBD region at a Reynolds number of 100 in microchannels is expected to undergo further refinement as new data become available in this range of flow.

NOMENCLATURE

As =

heat transfer surface area, m2

Bo=

boiling number, q″/(G iLG)

Co=

convection number, (ρGL)0.5 ((1 − x)/x)0.8

Dh =

tube diameter, mm

f=

fanning friction factor

FFl =

fluid-surface parameter

Fr=

Froude number

G=

mass flux, kg/m2 s

hLO =

all-liquid flow single-phase heat transfer coefficient, W/m2 °C

hTP =

two-phase heat transfer coefficient, W/m2 °C

iLG =

specific enthalpy, J/kg

k=

thermal conductivity of liquid, W/m °C

L=

length of tube, m

Nu=

Nusselt number

Pavg =

test section average pressure, kPa

q″=

heat flux, W/m2

ReLo =

all-liquid flow Reynolds number

T=

temperature, °C

X=

quality

Greek

μ=

viscosity, Ns/m2

ρ=

density, kg/m3

Subscripts

avg=

average

TS=

test section

NBD=

nucleate boiling dominant

CBD=

convective boiling dominant

Acknowledgments

All of the work was conducted in the Thermal Analysis and Microfluidics Laboratory at RIT. The support provided by Rochester Institute of Technology is gratefully acknowledged.

REFERENCES

  • Kandlikar , S. G. 1990 . A General Correlation for Two-Phase Flow Boiling Heat Transfer Coefficient Inside Horizontal and Vertical Tubes . J. Heat Transfer , vol. 102 : pp. 219 – 228 .
  • Kandlikar , S. G. 1991 . A Model for Predicting the Two-Phase Flow Boiling Heat Transfer Coefficient in Augmented Tube and Compact Heat Exchanger Geometries . J. Heat Transfer , vol. 113 : pp. 966 – 972 .
  • Kandlikar , S. G. and Grande , W. J. 2003 . Evolution of Microchannel Flow Passages—Thermohydraulic Performance and Fabrication Technology . Heat Transfer Engineering , vol. 25 ( no. 1 ) : pp. 3 – 17 .
  • Petukhov , B. S. and Popov , V. N. 1963 . Theoretical Calculation of Heat Exchange in Turbulent Flow in Tubes of an Incompressible Fluid with Variable Physical Properties . Teplofiz. Vysok. Temperature (High Temperature Heat Physics) , vol. 1 ( no. 1 ) : pp. 69 – 83 .
  • Gnielinski , V. 1976 . New Equations for Heat and Mass Transfer in Turbulent Pipe and Channel Flow . International Chemical Engineer , vol. 16 : pp. 359 – 368 .
  • Schrock , V. E. and Grossman , L. M. 1962 . Forced Convective Boiling in Tubes . Nuclear Science and Engineering , vol. 12 : pp. 474 – 481 .
  • Kandlikar , S. G. and Nariai , H. 1999 . “ Flow Boiling in Circular Tubes ” . In Handbook of Phase Change , Edited by: Kandlikar , S. G. pp. 367 – 441 . Philadelphia, PA : Taylor and Francis . Chapter 15
  • Kandlikar , S. G. 1991 . Development of a Flow Boiling Map for Subcooled and Saturated Flow Boiling of Different Fluids in Circular Tubes . J. Heat Transfer , vol. 113 : pp. 190 – 200 .
  • Kandlikar , S. G. , Cartwright , M. D. and Mizo , V. R. 1995 . “ A Photographic Study of Nucleating Bubble Characteristics in Flow Boiling, Convective Flow Boiling ” . In Proceedings of Convective Flow Boiling , pp. 73 – 78 . Taylor and Francis . the Banff Center for Conferences, Banff, Alberta, Canada, April 30–May 5
  • Kandlikar , S. G. 1998 . Heat Transfer and Flow Characteristics in Partial Boiling, Fully Developed Boiling, and Significant Void Regions of Subcooled Flow Boiling . ASME J. of Heat Transfer , vol. 120 : pp. 395 – 401 .
  • Kandlikar , S. G. and Steinke , M. E. January 24–29, 2003 . “ Predicting Heat Transfer During Flow Boiling in Minichannels and Microchannels ” . In ASHRAE Annual Meeting Chicago
  • Kandlikar , S. G. and Steinke , M. E. August 19–23, 2002 . “ Flow Boiling Heat Transfer Coefficient In Minichannels—Correlation and Trends ” . In 12th International Heat Transfer Conference Grenoble, , France
  • Wambsganss , M. W. , France , D. M. , Jendrzejczyk , J. A. and Tran , T. N. 1993 . Boiling Heat Transfer in a Horizontal Small-Diameter Tube . J. Heat Transfer , vol. 115 : pp. 963 – 972 .
  • Lin , S. , Kew , P. A. and Cornwell , K. 2001 . Flow Boiling of Refrigerant R141B in Small Tubes . Trans IChemE 79 , : pp. 417 – 424 .
  • Kandlikar , S. G. and Balasubramanian , P. 2003 . “ Extending the applicability of flow boiling correlation in microchannels ” . In First Int. Conf. Micro and Minichannels pp. 603 – 6082 . Rochester, NY April 24–25
  • Yen , T.-H. , Kasagi , N. and Suzuki , Y. 2002 . “ Forced Convective Boiling Heat Transfer in Microtubes at Low Mass and Heat Fluxes ” . In Compact Heat Exchangers Edited by: Celata , G. P. , Thonon , B. , Bontemps , A. , Kandlikar , S. G. and Edizioni , ETS . Pisa, , Italy A Festschrift on the 60th Birthday of Shah, R. K.

Reprints and Corporate Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

To request a reprint or corporate permissions for this article, please click on the relevant link below:

Academic Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

Obtain permissions instantly via Rightslink by clicking on the button below:

If you are unable to obtain permissions via Rightslink, please complete and submit this Permissions form. For more information, please visit our Permissions help page.