Occupational Exposure to Power Frequency Fields in Some Electrical Transformation Stations in Romania

&
Pages 149-153 | Published online: 08 Jan 2015
 

Abstract

The aim of this study is to investigate the levels of electric and magnetic power frequency fields at 8 electrical transformation stations in the North-East counties of Romania and to check their compliance with standards. Spot measurements were carried out on both electric and magnetic fields under overhead conductors of 110-, 220- and 380-kV installations. The magnetic field levels were several orders of magnitude below the reference level for occupational exposure set by ICNIRP (International Commission on Non-Ionizing Radiation) or by Romanian regulations. In contrast, the electric field levels were about the same order of magnitude as the reference levels. In 2 electrical stations the reference level of 10 kV/m was exceeded at specific locations within the outdoor installations area. However, the additional reference level for short-time exposure included in Romanian regulations, 30 kV/m, was not exceeded.

Reprints and Corporate Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

To request a reprint or corporate permissions for this article, please click on the relevant link below:

Academic Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

Obtain permissions instantly via Rightslink by clicking on the button below:

If you are unable to obtain permissions via Rightslink, please complete and submit this Permissions form. For more information, please visit our Permissions help page.