Improved Local Exhaust Control by Directed Push-Pull Ventilation system

&
Pages 59-65 | Published online: 04 Jun 2010
 

Abstract

Experiments using the directed push-pull ventilation technique were conducted on a general type of local exhaust ventilation installation. The exhaust (pull) system consisted of a square hood, while the push system consisted of one or two slot jets or two round jets. The two slot or round jets were located behind and beside a mannequin (the mannequin simulated the worker's position). The one slot jet was located between the smoke source and the mannequin. Under experimental conditions, the push-pull system reduced the amount of smoke in the mannequin's breathing zone even when the exhaust system volume flow rate necessary for capture of the smoke decreased approximately 50%. Generally, no difference between the slot and round jet control performance was found. The experiments showed that the directed push-pull ventilation system can be used effectively to reduce the contaminant emission into a workroom, if the jets are located so that the eddy currents induced by the worker or other obstructions are minimized or eliminated.

Reprints and Corporate Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

To request a reprint or corporate permissions for this article, please click on the relevant link below:

Academic Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

Obtain permissions instantly via Rightslink by clicking on the button below:

If you are unable to obtain permissions via Rightslink, please complete and submit this Permissions form. For more information, please visit our Permissions help page.