142
Views
3
CrossRef citations to date
0
Altmetric
Original Articles

Real-Time Evaluation of Ventilation Filter-Bank Systems

, , , &
Pages 58-69 | Published online: 07 Apr 2011
 

Abstract

This study evaluated two government facility ventilation systems. One was a metropolitan government office complex with a recirculation system where outside air was the makeup air; the other was a NIOSH facility that used 100% outside air with no recirculation. The methodology employed was a modified American Society of Agricultural Engineers standard (S525) for testing total enclosure filtration efficiency, in agricultural tractor cabs, with optical particle counters (OPC). The low-efficiency bag filters were tested when new and after being in the ventilation system for 3 months. The replacement medium-efficiency filters were evaluated for 6 months (the manufacturer's suggested change-out schedule). These eight-chamber, medium-efficiency filters had an increased filter surface area that resulted in increased airflow through the system. Unfortunately, these filters contained electrostatic filter media and lost filtration efficiency rapidly, which was subsequently confirmed in a 30-day study conducted to determine an appropriate change-out schedule for the eight-chamber bag filters. The study determined that less than 6 months' use was justified due to the reduced efficiency of the electrostatic filter media. The NIOSH facility's air handler #8 (100% outside air unit) was upgraded from electrostatic bag filters, which had a suggested 9-month change-out schedule, to V Bank mechanical, wet-laid, glass fiber filters. The results of a 3-year evaluation showed that the V Bank filters had better filter efficiency after 3 years of service than the electrostatic filters had at 9 months. Both studies employed matched OPC instruments to reduce instrument-to-instrument bias. The methodology is adaptable to monitoring the total efficiency of most air filtration systems, and results can help make decisions about upgrading filter performance

ACKNOWLEDGMENTS

The authors thank Dr. William Miller (NIOSH) for his contributions to the statistical analysis done in conjunction with these surveys.

The findings and conclusions in this report are those of the authors and do not necessarily represent the views of the National Institute for Occupational Safety and Health.

Notes

AThe data are averages of all 1-min samples collected over 2-day periods.

AThe data are averages of all 1-min samples collected over 2-day periods.

AThe data are averages of all 1-min samples collected continuously for 30 days.

AThe data are averages of all 1-min samples collected.

AThe data are averages of all 1-min samples collected.

Reprints and Corporate Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

To request a reprint or corporate permissions for this article, please click on the relevant link below:

Academic Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

Obtain permissions instantly via Rightslink by clicking on the button below:

If you are unable to obtain permissions via Rightslink, please complete and submit this Permissions form. For more information, please visit our Permissions help page.