Abstract
This article compares two modeling approaches for optimal operation of a turbo chiller installed in an office building: (1) a machine learning model developed with artificial neural network (ANN) and (2) a hybrid machine learning model developed with the ANN model and available physical knowledge of the chiller. Before developing the ANN model of the chiller, the authors used Gaussian mixture model in order to check the validity of measured data. Then, the hybrid model was developed by combining the ANN model and physics-based regression equations from the EnergyPlus engineering reference. It was found that both the ANN and hybrid ANN model are satisfactory to predict the chiller’s power consumption: mean bias error (MBE) = −2.63%, coefficient of variation of the root mean square error (CVRMSE) = 8.05% by the ANN model; MBE = −3.99%, CVRMSE = 11.98% by the hybrid ANN model. However, the hybrid model requires fewer inputs (four inputs) than the ANN model (eight inputs). The energy savings of both models are similar coefficient of performance (COP) = 4.32 by the optimal operation of the ANN model; COP = 4.44 by the optimal operation of the hybrid ANN model. In addition, the hybrid ANN model can be applied where the ANN model is unable to provide accurate predictions.