Zoned exponential, vertical and horizontal ultra-clean laminar airflows: No differences in bacteriological efficiency

, &
Pages 169-172 | Received 25 Apr 1997, Accepted 09 Nov 1997, Published online: 08 Jul 2009
 

Abstract

We compared the novel zoned exponential ultra-clean operating room ventilation, needing no extra side-walls with the traditionally used ultra-clean air systems having vertical or horizontal laminar airflow, but requiring extra side-walls. The three units were evaluated with regard to elimination of particles with focus on airborne and sedimenting bacteria-carrying particles (colony forming units, cfu) during rigidly standardized sham operations. Although minor differences were recorded inside the ultra-clean air-flows, the three systems were comparable with regard to bacteriological efficiency and ensured a low air and surface contamination (0.05-4 cfu/m3 and 7-72 cfu/m2/h, depending on the site of sampling).

We conclude that all three systems fulfilled well the criteria for ultra-clean air (< 10 cfu/m3), but that exponential airflow is the most versatile alternative, as additional side-walls around the operating area can be omitted.

Reprints and Corporate Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

To request a reprint or corporate permissions for this article, please click on the relevant link below:

Academic Permissions

Please note: Selecting permissions does not provide access to the full text of the article, please see our help page How do I view content?

Obtain permissions instantly via Rightslink by clicking on the button below:

If you are unable to obtain permissions via Rightslink, please complete and submit this Permissions form. For more information, please visit our Permissions help page.