Abstract
The two-phase heat transfer coefficients of R404A and R134a in a smooth tube of 7.49-mm inner diameter were experimentally investigated at low heat and mass flux conditions. The test section is a 10-m-long counter-flow horizontal double-tube heat exchanger with refrigerant flow inside the tube and hot fluid in the annulus. The heat transfer coefficients along the length of the test section were measured experimentally under varied heat flux conditions between 4 and 18 kW m−2 and mass flux ranging between 57 and 102 kg m−2 s−1 (2.5 to 4.5 g s−1) for saturation temperatures of −10°C, −5°C, and 0°C. The saturation temperatures correspond to pressures of 4.4, 5.2, and 6.1 bar for R404A and 2.0, 2.4, and 3.0 bar for R134a, respectively. The results showed that under the tested conditions, the contribution of the nucleate boiling mechanism is predominant in the heat transfer coefficient throughout the flow boiling process. The Kattan–Thome–Favrat flow pattern maps confirm the occurrence of stratified and stratified-wavy flow patterns for all of the tested conditions. The average heat transfer coefficient of R404A is estimated to be 26 to 30% higher than that of R134a for the same saturation temperature.