A novel approach to the data center hybrid cooling design with containment

, &
Pages 477-487 | Received 06 Sep 2016, Accepted 28 Nov 2016, Published online: 09 Mar 2017
 

ABSTRACT

Hybrid cooling solutions, which consist of the installation of heat exchangers near IT equipment, aim to eliminate hot spots in data centers containing high-density computer cabinets. In addition, cold aisle containment is often used to reduce hot air recirculation to improve energy efficiency. However, the viability and efficiency of each hybrid cooling strategy with or without containment depend on the IT load and equipment arrangement, and no formal procedure exists for selecting the most efficient strategy for a given application. Therefore, this study provides a computational approach for ranking the performance of different cooling strategies based on their capacity and cooling efficiency. The results of analyses indicate that applying containment is beneficial in (1) lowering the maximum temperature of the air entering the racks as airflow rates are increased, and (2) increasing the uniformity of rack inlet temperatures. However, applying containment also requires additional mechanical work by the computer room air handler (CRAH) fan, which may raise the data center power usage effectiveness (PUE). Application of the computational approach discussed here highlights the use of hybrid cooling to lower PUE by reducing the CRAH fan power.

Nomenclature

Latin letters=
cp=

specific heat capacity at constant pressure, J/kg K

COP=

coefficient of performance, dimensionless

g=

gravitational acceleration, m/s2

HP=

pump head, m

=

mass flow rate, kg/s

P=

power, W

T=

temperature, K

=

rack heat load, W

=

heat removal from chiller, W

=

hybrid cooler heat removal, W

Vin=

CRAH inlet air velocity, m/s

=

volume flow rate, m3/s

a=

nonuniformity value, dimensionless

μ=

dynamic viscosity, kg/m.s

ρ=

density, kg/m3

η=

efficiency, dimensionless

=

exergy destruction, W

Subscripts=
a=

air

ai=

air inlet

ao=

air outlet

avg=

averaged value

ch=

chilled water

CFD=

computational fluid dynamics

FN=

flow network

IT=

IT equipment

HC=

hybrid cooler property

max=

maximum

Nomenclature

Latin letters=
cp=

specific heat capacity at constant pressure, J/kg K

COP=

coefficient of performance, dimensionless

g=

gravitational acceleration, m/s2

HP=

pump head, m

=

mass flow rate, kg/s

P=

power, W

T=

temperature, K

=

rack heat load, W

=

heat removal from chiller, W

=

hybrid cooler heat removal, W

Vin=

CRAH inlet air velocity, m/s

=

volume flow rate, m3/s

a=

nonuniformity value, dimensionless

μ=

dynamic viscosity, kg/m.s

ρ=

density, kg/m3

η=

efficiency, dimensionless

=

exergy destruction, W

Subscripts=
a=

air

ai=

air inlet

ao=

air outlet

avg=

averaged value

ch=

chilled water

CFD=

computational fluid dynamics

FN=

flow network

IT=

IT equipment

HC=

hybrid cooler property

max=

maximum

Acknowledgments

We sincerely appreciate the support and help provided by Future Facilities.

Log in via your institution

Log in to Taylor & Francis Online

PDF download + Online access

  • 48 hours access to article PDF & online version
  • Article PDF can be downloaded
  • Article PDF can be printed
USD 61.00 Add to cart

Issue Purchase

  • 30 days online access to complete issue
  • Article PDFs can be downloaded
  • Article PDFs can be printed
USD 716.00 Add to cart

* Local tax will be added as applicable

Related Research

People also read lists articles that other readers of this article have read.

Recommended articles lists articles that we recommend and is powered by our AI driven recommendation engine.

Cited by lists all citing articles based on Crossref citations.
Articles with the Crossref icon will open in a new tab.