Experimental Validation of a Target Method for Balancing Exhaust Ventilation Duct Systems with Dampers

&
Pages 689-701 | Published online: 24 Sep 2008
 

Abstract

This study tested the “Target Method” for adjusting ventilation systems. The Target Method is based on target hood static pressures (SPh target ) computed in a manner designed to take into account the estimated effects of dampers on the fan, the order of damper adjustments, and the ratio of the prebalancing branch airflows to their goals. It is aimed at achieving a desired relative distribution of airflows even if the fan output is far from ideal. The method assumes the fan output will be adjusted after the dampers are adjusted. The method is expected to produce lower fan pressure requirements than some commonly used methods. The method was tested on a working seven-branch, full-sized exhaust ventilation system in the West Virginia University Exposure Assessment Laboratory. Two radically different target distributions were tested with two replications apiece. Both target distributions of airflows were substantially different from the initial distribution, providing a high degree of challenge to the methodology. For each distribution, SPh target values were computed for the first round of adjustments. Each damper was adjusted until the observed value of the hood static pressure was nearly equal to that damper's computed SPh target value for that distribution. Each of the other branch dampers was adjusted similarly in turn. After the first round of adjustments, the median ratio of SPh to SPh target provided the targets for the partial second round of adjustments. Twenty-point Pitot traverses were used to determine the airflow in each branch duct both before and after employing the adjustment method, providing the basis to determine the success in reaching each of the two desired distributions. The percentage of excess airflow (assuming ideal adjustment of the fan speed) was below 2.2% for all experimental trials. An unpublished study by Vivek Balasubramanian showed that excess airflow was 4.8% to 8.5% in the same experimental system after two full rounds of adjustment using the customary Target Method. Under poor measurement conditions, the greater uncertainty of pressure measurements would likely produce somewhat higher excess airflows.

ACKNOWLEDGMENTS

The authors wish to thank Nordfab Inc (Thomasville, N.C.) for donating the ductwork; Ahmed El-Sotouhy and Vivek Balasubramanian for their help in building the ventilation system; and Vivek Balasubramanian for testing the Goal Method.

Log in via your institution

Log in to Taylor & Francis Online

PDF download + Online access

  • 48 hours access to article PDF & online version
  • Article PDF can be downloaded
  • Article PDF can be printed
USD 61.00 Add to cart

Issue Purchase

  • 30 days online access to complete issue
  • Article PDFs can be downloaded
  • Article PDFs can be printed
USD 148.00 Add to cart

* Local tax will be added as applicable

Related Research

People also read lists articles that other readers of this article have read.

Recommended articles lists articles that we recommend and is powered by our AI driven recommendation engine.

Cited by lists all citing articles based on Crossref citations.
Articles with the Crossref icon will open in a new tab.