289
Views
5
CrossRef citations to date
0
Altmetric
Original Articles

Removal and Leakage of Environmental Tobacco Smoke from a Model Smoking Room

, , , &
Pages 573-584 | Published online: 06 Aug 2010
 

Abstract

Experimental studies on the removal of accumulated environmental tobacco smoke (ETS) and the effectiveness of ETS leakage control were carried out in a model smoking room using carbon monoxide, nicotine, 3-ethenylpyridine, respirable suspended particulates, and ultrafine particles (UFP) as the ETS tracers. The study investigated the effectiveness of the designated smoking room, equipped with a displacement ventilation system under different ventilation rates (10–58 L/sec per person,) in removing the ETS tracers. The extent of ETS leakage through different door operating scenarios under various ventilation rates was intensively studied. In particular, a manikin installed on a motorized rail was used to study the effect of human movement on the leakage of the ETS tracers. A double-door anteroom design was incorporated into the smoking room to study its effectiveness in ETS leakage prevention. It shows that at least 5 Pa of negative pressure, a fresh air supply rate 3–5 times higher than a typical office, direct air exhaust without air recirculation, and keeping the door closed are important for reducing ETS leakage. However, with the smokers moving in and out and the opening of the door, noticeable leakage of ETS can occur. The double-door anteroom design can improve leakage prevention. Among the five tracers, nicotine required the longest purging time to remove, after the smoking activity was stopped in the smoking room, due to its highly sorptive property. At least 4.4–6 hr of purging is needed for minimizing ETS exposure by non-smokers entering the smoking room. The peak size of particulate matter inside the smoking room is about 80–100 nm, suggesting the importance of including UFP as an indicator for monitoring the exposure and leakage of ETS. The impact of manikin movement on contaminant transport was studied, providing useful information on the effects of human activities on indoor air quality multicompartmental modeling.

ACKNOWLEDGMENT

This project was funded by the Hong Kong Food and Health Bureau, HKSAR Government, via a research contract by the Electrical and Mechanical Services Department (EMSD). The ultrafine particle measurements were supported by a general research fund grant, 611308, provided by the Hong Kong Research Grants Council. Technical support in both numerical and experimental studies from Wing Tong Leung and Gin Nam Sze To is highly appreciated.

Notes

A Only one sample was collected.

*p-value of H0: M = 0; Ha: M < 0.

A Coutside of CO was below MDL (0.1 ppm).

B The averaged Coutside was negative after subtracting the background level. Coutside/Cinside ratio was regarded as 0.

A H0: k = 0, H a : k > 0.

B MDL of nicotine = 0.1 μg/m3.

Log in via your institution

Log in to Taylor & Francis Online

PDF download + Online access

  • 48 hours access to article PDF & online version
  • Article PDF can be downloaded
  • Article PDF can be printed
USD 61.00 Add to cart

Issue Purchase

  • 30 days online access to complete issue
  • Article PDFs can be downloaded
  • Article PDFs can be printed
USD 148.00 Add to cart

* Local tax will be added as applicable

Related Research

People also read lists articles that other readers of this article have read.

Recommended articles lists articles that we recommend and is powered by our AI driven recommendation engine.

Cited by lists all citing articles based on Crossref citations.
Articles with the Crossref icon will open in a new tab.