Abstract
CO2-based demand-controlled ventilation (DCV) has been proved to be energy-efficient by altering ventilation rates according to surrogated indications of CO2 levels in single- and multiple-zone single-path variable air volume (VAV) systems. However, DCV for multiple-zone VAV systems with multiple recirculation paths is still untapped. Multiple-zone VAV systems with series and parallel fan-powered terminal units (FPTUs) are studied in this study. Energy and ventilation performance of the DCV strategies with dynamic resets are evaluated. The DCV control sequences for FPTUs are first summarized. A co-simulation approach combining EnergyPlus with CONTAM is adopted. The DCV controls are implemented in the EnergyPlus energy management system (EMS) module. New EnergyPlus EMS actuators are added and a customized EnergyPlus module is built to achieve the DCV control for each system. An office building is used to demonstrate the benefits from the proposed DCV strategies in four different U.S. climates zones. Two baselines for ventilation requirements (ASHRAE 62.1, California Title 24) are considered. The proposed DCV strategies resulted in 7–14% and 7–21% HVAC energy savings for each system, on a source energy basis, compared with the baseline of a simplified ASHRAE 62.1 approach. Both systems could achieve good compliance with the ventilation requirements in ASHRAE Standard 62.1.
Nomenclature
Cpr | = | concentration of CO2 in the primary air, ppm |
Cret | = | concentration of CO2 in the return air at the air handler, ppm |
Ep | = | primary air fraction, the fraction of primary air in the discharge air to the ventilation zone |
Ez | = | zone air distribution effectiveness, a measure of the effectiveness of supply air distribution to the breathing zone |
Fa | = | supply air fraction, the fraction of supply air in the ventilation zone, including sources of air from outside the zone: Fa = Ep + (1 – Ep) |
Fb | = | mixed-air fraction, the fraction of supply air in the ventilation zone from the fully mixed primary air: Fb = Ep |
Fc | = | outdoor air fraction, the fraction of outdoor air in the ventilation zone, including sources of air from outside the zone: Fc = 1 – (1 – Ez) |
Vbz | = | breathing zone outdoor airflow, cfm |
Vbz-P | = | population component of the breathing zone outdoor airflow |
Vbz-A | = | area component of the breathing zone outdoor airflow |
Vdz | = | zone discharge airflow, cfm |
Vds | = | system discharge airflow, which is the sum of all the zone discharge airflow, cfm |
Vpz | = | zone primary air |
Vou | = | uncorrected outdoor air rate, cfm |
Vot | = | outdoor air intake, cfm |
Xs | = | system level average outdoor air fraction |
Zdz | = | zone discharge air fraction, the fraction of the zone outdoor airflow in the zone cooling airflow |
Zpz | = | zone primary air fraction, the fraction of the zone outdoor airflow in the zone primary airflow |
Zd | = | system-level discharge air fraction |
Zp | = | system-level primary air fraction |
Acknowledgments
This work was funded by American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) through research project 1819: CO2 Demand Controlled Ventilation in Multiple Zone VAV Systems with Multiple Recirculation Paths.